RCD Testing Rig Overview - Pulsed DC on Type AC RCD Fails to Trip
John Ward
Overview of a testing arrangement and some quick tests to demonstrate the effect of pulsed DC on a type AC RCD. The black box is used to create a fault to earth, equivalent to the insulation in the heater being defective. Fault current shown on the multimeter in mA. This test places a single diode in series with the heater, effectively running it on half power on pulses of DC at 50Hz. This arrangement was commonly used in heaters to provide a full/half power option with a single switch.